HR Humidity Recessed - Obsolete
Key Points
- 2% or 3% accuracy
- 0-5/10V RH/Temp (thermistors optional)
- Field-calibration mode for offsets
- Durable and attractive low-profile design
Applications
- HVAC room humidity and temperature measurement and control
- Energy management/building control
The HR series is designed for use in energy management systems in buildings. They combine excellent stability with reliable operation and the digital provision to offset the RH reading +/-5% for in-field calibration. Thermistor options accommodate any installation. All versions also have surface mount trim ring for hard walls, and a metal ring for drywall recess without j-box.
Product improvement is a continuing process at Senva. The following products have been discontinued.
Improved Products.
SPECIFICATIONS |
Power Supply |
|
12-30VDC/24VAC (1), 15mA max. |
Outputs |
RH% and Temperature |
3-wire 0-5/10VDC (4) (jumper selectable) |
Output scaling |
RH% |
0-100% RH |
Temperature |
50-95° F (10-35° C) or 32-122°F (0-50°C) |
Thermistor Options |
|
Yes, see ordering table |
Media filter |
|
PTFE membrane, IP54 protection |
Relative Humidity |
Accuracy |
2% models: ±2% max 0 to 100% RH, ±1.5% typ 0 to 80% RH@25°C |
3% models: ±3% max 0 to 100% RH, ±2% typ 0 to 100% RH@25°C |
Resolution |
0.01%RH |
Hysteresis |
±0.8%RH |
Non-Linearity |
factory linearized <1%RH |
Temperature coefficient |
fully compensated by on-board temp sensor |
Response time (2) |
8s |
Output update rate |
0.5s |
Operating range |
0 to 100%RH (non-condensing) |
Long term drift |
<0.25%RH per year |
Normal Operating conditions (3) |
41 to 140°F (5 to 60°C) @ 20 to 80%RH |
Temperature |
Accuracy |
2% models, <±1° C; 0.5° C typ @ 25°C |
3% models, <±2° C; 0.5° C typ @ 25°C |
Resolution |
0.01° C |
Repeatability |
0.04° C |
Response time (2) |
2s |
Temperature Scaling |
50-95°F (10-35° C) |
Output update rate |
0.5s |
Operating range |
-40° C to 140°F (-40 to 60°C) |
- One side of transformer, secondary is connected to signal common. Dedicated transformer is recommended.
- Time for reaching 63% of reading at 25° C and 1 m/s airflow.
- Long term exposures to conditions outside normal range at high humidity may temporarily offset the RH reading (+3%RH after 60 hours).
- 15-30VDC/24VAC power supply voltage required for 10 volt output.