Power Supply
|
Comms
|
16-30VDC/24VAC(1), 5W max, 200mA max.
|
Analog
|
12-30VDC/24VAC(1), 5W max, 200mA max.
|
Wiring
|
Conductor
|
14-24 AWG, Minimum 600V, 75°C
|
Terminal Torque
|
0.5 N•m
|
Outputs (Analog)
|
2 programmable outputs
|
0-10V, 0-5V, and 4-20mA(2) (selectable)
|
CO Output Scaling
|
0-200ppm (default), 0-500ppm (menu selectable)
|
NO2 Output Scaling
|
0-10ppm (default), 0-10ppm (menu selectable)
|
CO2 Output Scaling
|
0-10,00ppm (default), 0-10,00ppm (menu selectable)
|
Propane/Methane/Hydrogen Output Scaling
|
0-50% LEL (default), 0-50% LEL (Menu Selectable)
|
Oxygen Output Scaling
|
0-25% Vol (default), 0-25% Vol (menu selectable)
|
Refrigerant Output Scaling
|
0-1000ppm (default), 0-1000ppm (menu selectable)
|
H2S Output Scaling
|
0-100ppm (default), 0-100ppm (menu selectable)
|
Ammonia NH3 Output Scaling
|
0-100ppm (default), 0-100ppm (menu selectable)
|
Temp Output Scaling (optional)
|
20 to 85°C
|
BACnet /Modbus
|
Protocol RS-48
|
BACnet MS/TP, Modbus RTU
|
Baud Rates
|
9600, 19200, 38400, 57600, 76800, 115200
|
RS-485
|
1/4 unit
|
Trouble Relay
|
Trouble Relay characteristics
|
N.C. 1A@24VAC/30VDC (50/60Hz) (no mains connection)
|
Alarm Relay
|
Alarm relay characteristics
|
N.O. 1A@24VAC/30VDC (50/60Hz) (no mains connection)
|
LED
|
Green, Yellow, Red
|
Green = Normal, Yellow = Warning, Red = Alarm
|
Audible Alarm Exposure
|
85dB Piezo transducer
|
30 minutes above alarm setpoint per UL2075; tamper-proof silence/reset button (menu selectable)
|
CO Sensor Performance
|
Type
|
Electrochemical
|
Accuracy
|
±5% of default range(3) ±5%of reading above 200ppm
|
Resolution
|
1ppm
|
Certifications
|
UL2075 Listed Component
|
Life expectancy
|
>7 years
|
Recommended Calibration
|
Annual
|
Recommended Height
|
3 to 6 feet; coverage 5000-7500 sq ft.
|
NO2 Sensor Performance
|
Type
|
Electrochemical
|
Accuracy
|
±5% of default range(4) ±5%of reading above 20ppm
|
Resolution
|
0.1ppm
|
Life expectancy
|
>7 years
|
Recommended Calibration
|
Annual
|
Recommended Height
|
3 to 6 feet; coverage 5000-7500 sq ft.
|
Carbon Dioxide (CO2)
|
Type
|
Non-Dispersive Infrared (NDIR)
|
Accuracy (5)
|
±(30ppm +3% of reading) (400-2000ppm), @-10-50°C
±(50ppm +5% of reading) Standard (2000-5000ppm), @-10-50°C
±(50ppm+3% of reading) Dual Channel (2000-5000ppm), @-10-50°C
±(100ppm+10% of reading) (5000-10000ppm), @0-50°C
|
Drift with ABC disabled (6)
|
35ppm/month (6) (Standard) 5ppm/month (6) (Dual Channel)
|
Range
|
0-2000/5000ppm; Programmable up to 10,000ppm
|
Response time
|
30 s
|
Sample rate
|
1 s
|
Recommended Height
|
3 to 6 feet; coverage 5000-7500 sq ft.
|
Resolution
|
1 ppm
|
Life expectancy
|
15 years
|
Methane/Propane/Hydrogen Sensors Performance
|
Type
|
Catalytic
|
Detection Range
|
0-50% LEL (Lower Explosive Limit)
|
Accuracy
|
5% of range
|
Resolution
|
1%LEL
|
Life expectancy
|
>5 years
|
Recommended Calibration
|
Bump test annually, calibrate or replace if necessary (12)
|
Recommended Height
|
Hydrogen/Methane: 0.5 to 1 foot from ceiling; coverage 5000-7500 sq ft
Propane: 1-3 ft. above finished floor, coverage area 5000 sq. ft.
|
Oxygen Sensor Performance
|
Type
|
Electrochemical
|
Detection Range
|
0-25% Volume
|
Accuracy
|
±5% of range
|
Resolution
|
0.1%
|
Life expectancy
|
5 years
|
Recommended Calibration
|
Annual
|
Recommended Height
|
3 to 6 feet; coverage 5000-7500 sq ft
|
H2S Sensor Performance
|
Type
|
Electrochemical
|
Detection Range
|
0-100 ppm
|
Accuracy
|
±5% of range
|
Resolution
|
1 ppm
|
Life expectancy
|
5 years
|
Recommended Calibration
|
6 months
|
Recommended Height
|
3 to 6 feet; coverage 5000-7500 sq ft
|
Ammonia Sensor Performance
|
Type
|
Electrochemical
|
Accuracy
|
±5% of range
|
Resolution
|
0.1 ppm
|
Life expectancy
|
5 years
|
Recommended Calibration
|
6 months
|
Recommended Height
|
0.5 to 1 foot from ceiling; coverage 5000-7500 sq ft
|
Refrigerant Sensor Performance
|
Type
|
Electrochemical
|
Detection Range
|
0-25% Volume
|
Resolution
|
1 ppm
|
R134A Sensitivity (6)
|
@300ppm test gas: 450 ppm R410A, 425 ppm R407C, 400 ppm R404A, 370 ppm R22, 300 ppm R134A
|
Other detectable gases (8)
|
R407A, R407F, R427A, R452B, R507, R448A, R449A, R422A, R422D, R452A, R513A, R514A, R32
|
Life expectancy
|
>10 years (typical life expectancy for MOS sensors)
|
Recommended Calibration
|
6 months
|
Recommended Height
|
6 inches above floor; no more than 18 inches above lowest level of equipment location for leak detection; coverage 5000-7500 sq ft.
|
Max Elevation (9)
|
2629 m (8625 ft)
|
Operating Environment
|
Temperature, continuous
|
-20 to 50°C
|
Humidity
|
15-90% continuous, 0-99% intermittent
|
Max Elevation
|
2000m
|
Enclosure
|
Material
|
ABS/Polycarbonate
|
Dimensions
|
5.7”h x 3.0” x 1.8”d
|
Rating
|
IP20
|
Agency
|
Compliance
|
RoHS
|