Power Supply
|
Non-Display
|
16-30VDC/24VAC(1), 3.5W nominal, 4W max.
|
Interface
|
OLED (optional)
|
1.5” Organic LED Display, 128x128, color
|
Air Quality Ring
|
Color changing (red/yellow/green) LED Air Quality Ring
|
Analog Outputs (Analog or Dual version only)
|
Quantity
|
Up to 3 outputs
|
Source
|
CO2, RH%, Temp, TVOC, PM, CO, Ozone (selectable)
|
Scale
|
0-5V, 0-10V, 4-20mA (switch selectable, programmable per output)
|
Protocol Output (Comms or Dual version only)
|
Protocol
|
BACnet MS/TP or Modbus RTU
|
Connection
|
3-wire RS-485, with isolated ground
|
Data Rate
|
9600, 19200, 38400, 57600, 76800, 115200 (switch selectable)
|
Address Range
|
0-127
|
Relay
|
Type
|
Solid-state output, 1A @ 30VAC/DC, N.O.
|
Polarity
|
NO/NC (selectable)
|
Source
|
CO2 setpoint, RH setpoint, Temp setpoint, TVOC setpoint, PIR motion detection, Air Quality, off (selectable)
|
CO2 (Optional)
|
Type
|
Non-dispersive Infrared (NDIR)
|
Accuracy (Standard)
|
±(30ppm + 3% of reading) (400-2,000ppm), -10-50ºC, 0-85%RH
±(50ppm+ 5% of reading) (2,000-5,000ppm), -10-50ºC, 0-85%RH
>5,000ppm consult factory
|
Accuracy(Dual)
|
±(30ppm + 3% of reading) (0-2,000ppm), @ 0-50ºC
±(50ppm+ 3% of reading) (2,000-5,000ppm), @ -10-50ºC
±(100ppm+ 10% of reading) (5,000-10,000ppm), @ 0-50ºC
|
Drift with ABC disabled (Standard)
|
35ppm/month
|
Drift with ABC disabled (Dual Channel)
|
5ppm/month
|
Resolution
|
1 ppm
|
Range
|
0-2,000 PPM (Default) (Programmable up to 10,000ppm)
|
Response time
|
90 seconds to 90% reading
|
Sample rate
|
1s
|
Temp and Pressure Compensation
|
Yes, barometric pressure readable over comms
|
Relative Humidity (Optional)
|
Type
|
Digital CMOS
|
Accuracy(2)
|
2% models, +/-2% over 0 to 80%RH range
|
Resolution
|
0.05%RH
|
Response time (3)
|
30s
|
Sample rate
|
3s
|
Operating range
|
0 to 100%RH (non-condensing)
|
Operating conditions (4)
|
-4 to 140oF (-20 to 60° C) @ RH>90%; -4 to 176oF @ RH=50%
|
Temperature Transmitter
(Optional)
|
Type
|
Silicon Band-gap
|
Nominal Accuracy
|
±0.3° C (operating range)
|
Maximum Accuracy (2)
|
±0.5° C (at 25° C), ±1.0° C
|
Resolution
|
0.1° C
|
Response time
|
30s
|
Sample rate
|
3s
|
TVOC (Optional)
|
Type
|
MOS
|
Gas
|
Total VOC
|
Formaldehyde CH2O Sensitivity
|
Responsive to Formaldehyde concentrations 50-1000 ppb
|
Range
|
0-10,000 μg/m3
|
Response Time
|
<10s
|
Accuracy (5)
|
±20 μg/m3 + 15% at 1 to 500 μg/m3 (typical)
|
Output
|
0-2,000 μg/m3 (default) programmable up to 10,000 μg/m3
|
PMx (Optional)
CLASS 1 LASER PRODUCT
|
Type
|
Optical
|
Size Range
|
PM1.0, PM2.5, PM4.0, PM10.0
|
Scale
|
0-1,000 μg/m3
|
Lower detection limit
|
0.3 μm
|
Precision
|
±10 μg/m3 (0-100μg/m3); ±10% (100-1,000 μg/m3)
|
Long-Term Drift
|
±1.25 μg/m3 / year
|
Carbon Monoxide
|
Type
|
Electrochemical
|
Detection Range
|
0-200 ppm
|
Accuracy
|
5% of reading
|
Resolution
|
1 ppm
|
Response Time
|
60 seconds
|
Sensor Life
|
5 years
|
Certifications
|
UL2034 Recognized Component
|
Ozone
|
Type
|
PMOS
|
Ozone Detection Range
|
20-500 ppb
|
Accuracy
|
±15% of FS @ 20° C
|
Operating Environment
|
Temperature
|
-4 to 122° F (-20 to 50° C). Devices including PM or CO sensors rated (-10 to 50° C) CO sensors can intermittently operate down to –20°C.”
|
Humidity
|
0-95% non-condensing
|
Enclosure
|
Material
|
ABS/Polycarbonate
|
|
Dimensions
|
4.0”h x 4.4”w x 2.1”d (+6.8” probe)
|
|
Conduit Opening
|
Tapped 1/2” NPT
|
|
Rating
|
IP43 or NEMA 3R
|
|
Compliance
|
Agency
|
CE, RoHS
|