Power Supply
|
|
12-30VDC/24VAC(1), 100mA max.
|
Outputs
|
Analog CO2
|
0-5/10V/4-20mA (3-wire) |
Analog Scaling
|
0-2000, 5000, 10,000 (selectable) |
Programmable Relay
|
Solid-state output, 1A @ 30VAC/DC, N.O.
|
Analog LCD Menu Parameters (2)
|
Spt, Set point, Hi (On)
|
Sets relay turn-on threshold (800ppm default)
|
SPh, Set point, hysteresis (Off)
|
Sets the relay turn-off hysteresis (100ppm default)
|
SCL, Scaling
|
0-2000ppm or 0-5000ppm (2000ppm default)
|
AdJ, Adjustment
|
CO2 Offset adjustment +/-250ppm (0 default)
|
CAL, Auto Calibration Period
|
Off, 7 days, 14 days, 30 days, 60 days (off default)
|
LvL Analog Output Scale
|
5v 5.0V full scale, 10v 10.0V full scale (default)
|
RUN, Run Mode
|
Displays CO2
|
CO2
|
Type
|
Non-dispersive Infrared (NDIR)
|
Accuracy
|
±(30ppm+3% of reading) (0-2000ppm) ±(50ppm+5% of reading) (2000-5000ppm) ±(100ppm+10% of reading) (5000-10000ppm)
|
Range
|
0-2000/5000ppm; Programmable up to 10,000ppm
|
Response time
|
30 seconds
|
Sample rate
|
1 second
|
Operating Environment (5)
|
Temperature
|
-4 to 122F (-20 to 50C)
|
Humidity
|
0-95% non-condensing
|
Enclosure
|
Material
|
ABS Plastic
|
Dimensions
|
4.7”h x 2.9”w x 1.24" (0.48" wall profile)
|