Power supply Input
|
Line/High voltage
|
90VLN-600VLL (+20%), 50/60Hz, 1-3 phase
|
Power Consumption
|
4W Typ.
|
Frequency Range
|
50/60 Hz
|
Outputs
|
RS-485
|
2-wire, BACnet MS/TP, Modbus RTU, Modbus ASCII
|
Baud Rates
|
9600, 19200, 38400, 57600, 76800, 115200
|
RS-485 Loading
|
1/4 unit
|
Pulse Output
|
Dual Outputs
|
Import & Export Energy Outputs
|
Type
|
Solid state dry contact
|
Specifications
|
N.O and N.C. 300mA max, 40Vac/dc
|
Pulse scaling
|
0.01, 0.1, 1, 10, 100, 1k Wh/Pulse
|
Duration
|
10,25,50,100,250,500 (ms)
|
EMX Wiring Requirements
|
Conductor gauge
|
24-14 AWG; Power terminals: 24-12 AWG
|
Terminal torque rating
|
0.37 ft-lb (0.50 N•m)
|
Pulse Inputs
|
Input Rating
|
3.5 ± 0.5 VDC, short circuit current is 10mA max
|
Pulse Rate
|
50 Hz (default), configurable up to 500 Hz
|
Pulse Active
|
<100 Ohms
|
Pulse Undefined
|
100-1000 Ohms
|
Pulse Idle
|
>1000 Ohms
|
Service Types
|
Configurations
|
1Ph, 2Ph, 3Ph Wye (4-Wire), 3Ph Delta (3-Wire)
|
Voltages
|
90VL-N through 600VL-L
|
Frequency
|
45-65 Hz
|
Measurement
|
CAT lll
|
EMX Performance
|
Meter Accuracy
|
0.2% (ANSI C12.20 Class 0.2 standards)
|
System Accuracy
|
1% for V, A, kW, kVAR, kVA
|
Operating Environment
|
Operating Temperature
|
-22 to 158ºF (-30 to 70ºC)
|
Storage Temperature
|
-40 to 158ºF (-40 to 70ºC)
|
Humidity
|
0-95% non-condensing
|
Environmental Rating
|
IP20; Front display IP40
|
EMX Meter Enclosure
|
Material
|
Polycarbonate/ABS
|
Dimensions
|
3.55”h x 4.18”w x 2.26”d
|
DIN Rail Compatibility
|
PR30 (TS 35/F6)
|
Industrial Enclosure (Optional)
|
Environmental Rating
|
NEMA 4X/ IP65
|
Optional enclosure dimensions
|
7.78”h x 7.78”w x 4.8”d
|
Material
|
Polycarbonate
|
Compliance
|
Agency
|
UL Listed, cUL Listed, File E489498
|
Standards
|
CE, RoHS
|