Key Points
10A resistive rating
Hand Off Auto option with tamper resistant cover
Current run-status confirmation option
UL/ULC, CE listed
RoHS compliant
Applications
Command contactors
Control motors
Isolation
Device interlocking
Relay logic
Lighting load levels
The PR Series pilot relays are ideal multi-voltage input pilot duty relays that mount to existing panels to control loads. External enclosures are not required making them ideal for interfacing loads with building automation control systems. Featuring the highest output in the smallest package, integrated current sensing, and a secure tamper resistant HOA.
Chat with us , powered by LiveChat
Convenient and cost-effective control
Current sensor run status option
LED indicator
Multi-voltage coil input
Hand-Off-Auto switch option
Compact enclosure mounts externally for easy installation
Nipple mount to any electrical enclosure
Flexible tinned stranded wire… fits easily in tight spaces and provides secure connections to wire nuts
Concealed HOA switch with screw secured cover prevents tampering
Versions with Hand Off Auto (HOA) switch feature with secure screw cover door to prevent tampering
Eliminates costly system override related service calls
Current sensing run status confirmation
Provides feedback that pilot device relay coil is powered
SPECIFICATIONS
General
Environmental Operating
-30 to 60 o C (-22 to 140 o F), 10-95% RH non-condensing
Expected Relay Life
100,000 cycles electrical; 10,000,000 mechanical
LED
ON when energized
Device Wiring
16” minimum lead length; coil: 18AWG; contacts: 14AWG;
HOA monitor wires: 14 AWG; status: 18AWG
Field Wiring
Coil: 16AWG to 18AWG, Contacts: 14AWG to 16AWG
Certifications
UL1015
Dimensions
Small Enclosure
1.75”x3.0”x1.75” with 0.5” NPT nipple
Medium Enclosure
2.5”x4.0”x1.78” with 0.5” NPT nipple
CONTACT RATINGS(PRU1c)
10 Amp Resistive @ 277 VAC
10 Amp Resistive @ 28 VDC
480 VA Pilot Duty @ 240-277 VAC
480 VA Ballast @ 277 VAC
Not rated for electronic ballast
600 Watt Tungsten @ 120 VAC (N.O.)
240 Watt Tungsten @ 120 VAC (N.C.)
1/3 HP @ 120 VAC (N.O.)
1/6 HP @ 120 VAC (N.C.)
1/4 HP @ 277 VAC (N.O.)
1/8 HP @ 277 VAC (N.C.)
PR3_series
CONTACT RATINGS(PRU1s)
10 Amp Resistive @ 277 VAC
10 Amp Resistive @ 14 VDC
480 VA Pilot Duty @ 240-277 VAC
480 VA Ballast @ 277 VAC
Not rated for electronic ballast
600 Watt Tungsten @ 120 VAC (N.O.)
1/3 HP @ 120/240 VAC (N.O.)
1/4 HP @ 277 VAC (N.O.)
COIL CURRENT/Performanc e
Voltage
AC
DC
10 V
30mA
16mA
15 V
34mA
20mA
20 V
38mA
21mA
25 V
42mA
22mA
30 V
45mA
23mA
120 V
23mA
Pull-In Voltage
AC
DC
10 to 30V
8V
9V
120V
85V
Dropout Voltage
10 to 30V
3V
3V
PR4_series
COIL CURRENT/Performanc e
Voltage
AC
DC
10 V
30mA
16mA
15 V
34mA
20mA
20 V
38mA
21mA
25 V
42mA
22mA
30 V
45mA
23mA
120 V
23mA
Pull-In Voltage
AC
DC
10 to 30V
8V
9V
120V
85V
Dropout Voltage
10 to 30V
3V
3V