Key Points
Superior RH sensing
- On-board temperature compensation for RH.
- Gasket seals sensor against wall drafts and false readings
Choose from a range of accuracies and options
- 2% and 3% RH accuracy options
- 0-5V, 0-10V, 2-wire and 3-wire 4-20mA options
- Thermistor outputs for temperature optional
Superior RH sensing
- On-board temperature compensation for RH.
- Gasket seals sensor against wall drafts and false readings
Choose from a range of accuracies and options
- 2% and 3% RH accuracy options
- 0-5V, 0-10V, 2-wire and 3-wire 4-20mA options
- Thermistor outputs for temperature optional
SPECIFICATIONS |
Power Supply |
|
12-30VDC/24VAC (1), 24mA max. |
Outputs |
RH% (options) |
3-wire 0-5/10VDC, 4-20mA 2-wire 4-20mA |
Output scaling |
RH% |
0-100% RH |
Thermistor Options |
|
Yes, see ordering table |
Media filter |
|
PTFE membrane, IP54 protection |
Relative Humidity |
Accuracy |
2% models: ±2% max 0 to 100% RH |
3% models: ±3% max 0 to 100% RH |
Resolution |
0.01%RH |
Hysteresis |
±0.8%RH |
Non-Linearity |
factory linearized <1%RH |
Temperature coefficient |
fully compensated by on-board temp sensor |
Response time (2) |
8s |
Output update rate |
0.5s |
Operating range |
0 to 100%RH (non-condensing) |
Long term drift |
<0.25%RH per year |
Normal Operating conditions (3) |
41 to 140°F (5 to 60°C) @ 20 to 80%RH |
- One side of transformer, secondary is connected to signal common. Dedicated transformer is recommended.
- Time for reaching 63% of reading at 25° C and 1 m/s airflow.
- Long term exposures to conditions outside normal range at high humidity may temporarily offset the RH reading (+3%RH after 60 hours).
- 15-30VDC/24VAC power supply voltage required for 10 volt output.