Home > Humidity > Humidity - Room Recessed

Humidity - Room Recessed

  • 2 or 3% accuracy
  • 0-5V/10VDC RH/Temp (thermistors optional)
  • Field-calibration potentiometer
  • Durable and attractive low-profile design

Applications

  • HVAC room humidity and temperature measurement and control
  • Energy management/building control

Description

The HR series is designed for use in energy management systems in buildings. They combine excellent stability with reliable operation and provision to offset the RH reading +/-5% for in-field calibration. Thermistor options accommodate any installation. Housing is offered in multiple color choices to match any decor.

Product     Price   Quantity
HR-2A Room RH 2% RH Accuracy   $ 250.31
HR-2B Room RH/T-Transmitter2% RH Accuracy   $ 252.94
HR-2C Room RH/T-100pT2% RH Accuracy   $ 279.19
HR-2D Room RH/T-1000pT2% RH Accuracy   $ 279.19
HR-2E Room RH/T-10KT2 2% RH Accuracy   $ 334.24
HR-2F Room RH/T-10KT3 2% RH Accuracy   $ 334.24
HR-2G Room RH/T-10KT3 w/11K shunt2% RH Accuracy   $ 334.24
HR-2H Room RH/T-3K 2% RH Accuracy   $ 334.24
HR-2I Room RH/T-2K2 2% RH Accuracy   $ 334.24
HR-2J Room RH/T-1800R TAC2% RH Accuracy   $ 334.24
HR-2K Room RH/T-20K NTC2% RH Accuracy   $ 334.24
HR-2L Room RH/T-100K2% RH Accuracy   $ 334.24
HR-3A Room RH 3% RH Accuracy   $ 226.91
HR-3B Room RH/T-Transmitter3% RH Accuracy   $ 229.54
HR-3C Room RH/T-100pT3% RH Accuracy   $ 255.79
HR-3D Room RH/T-1000pT3% RH Accuracy   $ 255.79
HR-3E Room RH/T-10KT2 3% RH Accuracy   $ 240.79
HR-3F Room RH/T-10KT3 3% RH Accuracy   $ 240.79
HR-3G Room RH/T-10KT3 w/11K shunt3% RH Accuracy   $ 240.79
HR-3H Room RH/T-3K 3% RH Accuracy   $ 240.79
HR-3I Room RH/T-2K2 3% RH Accuracy   $ 240.79
HR-3J Room RH/T-1800R TAC3% RH Accuracy   $ 240.79
HR-3K Room RH/T-20K NTC3% RH Accuracy   $ 240.79
HR-3L Room RH/T-100K3% RH Accuracy   $ 240.79

CLICK ON LISTED ITEM FOR SPECIFICATIONS.

List prices shown; trade pricing appears on orderpad for Senva Trade Accounts.
For qualified trade pricing, please contact us at 866-660-8864.
Oregon has no sales tax.

Attractive recessed design is attractive and durable

  • Match colors and existing interior decor
  • Fits in most standard wall plates
  • No exposed screws; unobtrusive tamper resistant design
  • Ideal for schools

Field calibration poteniometer

  • Field calibration scaled adjustment allows easy adjustment of calibrated RH value as needed to maintain certification.
  • 0-5V/0-10V output—jumper selectable

Choose from a range of accuracy and options

  • 2% and 3% RH accuracy options
  • Thermistor outputs for temperature optional

Superior RH sensing

  • On-board temperature compensation for RH. Eliminates temperature coefficient errors and achieves an excellent measurement accuracy as well as high repeatability and offset stability. 
SPECIFICATIONS
Power Supply   12-30VDC/24VAC (1), 15mA max.
Outputs RH% and Temperature 3-wire 0-5/10VDC (4) (jumper selectable)
Output scaling RH% 0-100% RH
Temperature 50-95° F (10-35° C)
Thermistor Options   Yes, see ordering table below
Media filter   PTFE membrane, IP54 protection
Relative Humidity Accuracy 2% models, +/-2% over 10 to 90%RH range
3% models, +/-3% over 20 to 80%RH range
Resolution 0.05%RH
Hysteresis +/-1%RH
Non-Linearity factory linearized <1%RH
Temperature coefficient fully compensated by on-board temp sensor
Response time (2) 30s
Output update rate 2s
Operating range 0 to 100%RH (non-condensing)
Long term drift <0.5%RH per year
Operating conditions (3) -20° C to 60° C @ RH>90%
-20° C to 80° C @ RH=50%
Temperature Accuracy (-20° C to 70° C range) 2% models, <+/-1° C; 0.5° C typ @ 25° C
3% models, <+/-2° C; 0.5° C typ @ 25° C
Resolution 0.01° C
Repeatability +/-0.1° C
Response time (2) 30s
Temperature Scaling 50-95° F (10-35° C)
Output update rate 2s
Operating range -40° C to 120° C
  1. One side of transformer, secondary is connected to signal common. Dedicated transformer is recommended.
  2. Time for reaching 63% of reading at 25° C and 1 m/s airflow.
  3. Long term exposures to conditions outside normal range at high humidity may temporarily offset the RH reading (+3%RH after 60 hours).
  4. 15-30VDC/24VAC power supply voltage required for 10 volt output.